OPERATION
!
WARNING
All information in this manual is for
reference and guidance purposes,
and does not substitute for required
professional training, conduct, and strict
adherence to applicable jurisdictional/
professional codes and regulations.
Non-Fulton product information is for
reference purposes only. No Fulton
document should substitute for full review
of documentation available from the
component manufacturer.
3-14
` OUTDOOR RESET
Separately entries are available for Occupied and Unoccupied modes.
The hydronic loop temperature setpoint will be calculated based on configured
outdoor air and setpoint high and low temperature values. When the outdoor air
temperature reaches a warm weather shutdown Outdoor Air Cutoff temperature,
the boilers will be disabled until outdoor air temperature has decreased by the
value assigned in the Cutoff Reset.
` SCHEDULING
The Scheduling system allows for the operator to configure when the normal
(occupied) setpoint will be maintained. When outdoor reset is enabled, the
normal setpoint curve will establish setpoint during these time frames with the
setback (unoccupied) setpoint curve establishing setpoint for all other times.
ƒ Configuration
Functions are used during initial commissioning, troubleshooting and other
tasks.
` SYSTEM CONFIGURATION
The System Configuration screen is used for saving (backup) and loading of
program settings. The backup battery status is shown in the bottom right of the
screen. Loss of power without an operational battery will result in lost program
settings.
` SENSORS
An overview of boiler and auxiliary sensor status is available on this screen.
Sensor offset values may be configured for calibration purposes.
` USER CONFIGURATION
An administrator password can be assigned to the control to prevent
unauthorized access. The selected screens will require entry of the administrator
password prior to access. The password may be up to 10 characters in length.
SECTION 3
EXE-IOM-230112
© Fulton Group N.A., Inc. 2023