Example Of Basic Settings - Bentone B 65-2H Installation And Maintenance Instruction

Table of Contents

Advertisement

5.2

Example of Basic settings

Basic settings should only be seen as setting values to get burner to start.
Once the burner has started and established flame, it is necessary to adjust the
settings so that they are adapted to the installation and the fuel used.
B 65-2H
Burner output:
Estimated nozzle output:
(* Calorfic value Fuel oil
This provides the following nozzle according to the nozzle table, (see Technical
data).
941 kW distributed over 2 nozzles:
Nozzle, Stage 1:
Nozzle, Stage 2:
Pump pressure:
Setting values for 941 kW according to basic setting diagram, (see Technical
data).
Insert
Stage 2
Stage 1
Air
Air
Stage 2
Selection of output and connection between the different power stages must
be selected and adjusted so that the system achieves good functionality.
941 kW
941 / 11.86*
79.3 kg/h
=
11.86 kWh/kg)
=
11.00 Gph
575 kW
7.00 Gph
366 kW
14.0 bar
=
=
=
28
3
6.5
165 405 62