When the flow setpoint is modified, the icon
information on removing overrides, see How to release overrides .
The Flow parameter appears. This parameter represents the airflow as measured by the controller.
5. Monitor the Flow parameter until it stabilizes.
6. Using a flow hood, measure the actual airflow. Use the arrow keys to enter this measurement into
the Flow parameter.
7. Press the Menu button to submit the actual airflow.
The Damper parameter appears.
Note that at this point, the K-Factor gets adjusted based on the airflow value just entered.
8. Press the Menu button several times until the K-Factor parameter reappears. This value can be in-
cluded in the balancing report.
The VAV controller is now balanced.
ECB-VAVS Preloaded Applications