AUXILIARY POWER OUTPUTS

The
CBXi
and
FLX
modules each have two 18 V DC outputs, for I/O devices that require loop power.
For 3-wire connections return can be through any COM terminal, but it is recommended that Auxiliary
power wiring is through terminal 14, the COM between the two Auxiliary power terminals.
The DC output terminals provide a minimum of 18 V DC, but the combined load (on each IO module) must
remain below 60 mA.

USING A KEYPAD WITH THE CBXi

A
CBT-STAT
or
UCU Room Display
Note:
If
UCU Room Display
Setup.
©ABB 2022 All Rights Reserved.
Subject to change without notice
WWW.CYLON.COM
keypad can be connected to the
DS0064 UCU10FC/K
is used, refer to the
CBXi IP Controller |
CBX
at the CBT-STAT port.
for the corresponding Strategy Point