Installation

APPLY POWER TO THE CBXI-8R8(-H)

For the initial configuration of the device, the controller must first be powered on.
Service Port
(USB connection) must not be connected until after the device is powered on.
Note:
The
CBXi-8R8(-H)
conductor of the transformer must be grounded to an earth ground to avoid damage to the controller.
This conductor will be wired to the
here:
Ensure the 24 V AC/DC and
Note:
swapped, it may cause damage to anything connected to the controller.

CONNECT THE CBXi TO AN IP NETWORK

Place an Ethernet cable from the Network's Ethernet switch into one of the 2 Ethernet ports on the top of
the CBXi:
IP Cabling requirements
Cable
RJ-45 pin connections
Characteristic impedance
Distributed capacitance
Maximum Cable length
between IP devices
©ABB 2022 All Rights Reserved.
Subject to change without notice
WWW.CYLON.COM
requires 24 V AC/DC supplied from an externally mounted power transformer. One
(common) terminal of the controller. The wiring diagram is shown
COM
Common
wires are correctly connected to the controller. If the wires are
Standard patch cable, Cat 5e with 4 pairs of wires fitted with
RJ-45 connectors
Straight-through wiring
100-130 Ohms
Less than 100 pF per meter (30 pF per foot)
328 ft. (100 m) maximum
CBXi IP Controller |
Installation
30