CONNECT THE CBXi-8R8(-H) TO FLX UNITS

The I/O capabilities of a
devices.
These are connected to the
connector), one of which is shipped with each

SET THE FLX ADDRESS

Each of the
FLX
units connected to a single
bus. The address is set by the 5-way DIP switch.
The terminals on a
this address as illustrated below:
Inter-module bus
Address
00001
1
00010
2
00011
3
Note:
If there are 2 devices on the same
then the bottom (yellow) status LED will blink slowly to indicate a FLX bus address clash
©ABB 2022 All Rights Reserved.
Subject to change without notice
WWW.CYLON.COM
CBXi-8R8(-H)
can be extended by the addition of
CBXi-8R8(-H)
by means of a standard module interconnector
CBXi
FLX
unit will be accessible within the CBX Strategy with point numbers prefixed by
DIP switch
Point numbers
setting
101 ... 116
201 ... 216
301 ... 316
FLX bus
with the same address – including
CBXi IP Controller |
FLX
device.
must have an address that is unique on that CBXi's FLX
Installation
FLX-8R8
and
FLX-8R8-H
(FLX bus
, the address of the
CBXi
0
-
42