8-4 Upgrading from SL-1 XN (QCA55 cabinet) to Option 71

Upgrading from SL-1 XN to Meridian 1 Option 71

Shelf upgrades to Meridian 1 553-3001-253
1
Obtain printouts of all the characteristics (TN, loop, telephones and all
other assignments and features) of the existing system. Retain these
printouts for an after conversion check.
2
Using overlay program 43, perform a data dump.
3
Set ENB/DIS switch on all Power Monitor cards to DIS.
Load overlay program 35 and STAT CPU to determine which
CPU is active. If necessary switch CPU's (SCPU) to ensure that
system is operating in CPU 0.
Disable memory associated with CPU 1 (10, 11, 12, and so on).
Disable CMA 1.
Set ENB/DIS faceplate switches on the QPC215 SBE associated
with CPU 1 to DIS.
Load overlay program 39 and STAT SCG to determine which
SCG is active. If necessary switch SCG's (SCLK) to ensure that
system clock 0 is active.
Set Maintenance/Normal switch on CPU 0 to Maintenance.
4
Set CPU 1 breaker on the QBL21 power distribution box to OFF.
5
Disconnect cables from connectors A, B and C on the end of the
CPU 1 (QSD17 shelf).
6
Tag and disconnect the power monitor connector (connector D) and
power connector from the cabinet power wiring harness to the end of
the CPU 1 (QSD17 shelf).
Tag and disconnect cables from connectors on faceplates of circuit
packs on CPU 1 (QSD17 shelf).
Remove all circuit packs from CPU 1 (QSD17 shelf).
Note: The QPC215 SBE, QPC775 CC (or QPC471 CC) and the 5/12
V CONV circuit packs are required for the new CPU/MEM shelf. The
remaining packs removed should be packed and stored.