Configuration
(1)
Field settings are defined as follows:
• M: Mode number – First number: for group of units – Number between brackets: for individual unit
• SW: Setting number / C1: First code number
• —: Value number / C2: Second code number
: Default
Installer and user reference guide
74
M
C1/SW
13(23)
6
Time to clean air filter
This setting must correspond with the air contamination in the room. It determines
the interval at which the TIME TO CLEAN AIR FILTER notification is displayed on
the user interface. When using a wireless user interface, you must also set the
address (see the installation manual of the user interface).
If you want an interval of...
(air contamination)
±2500 h (light)
±1250 h (heavy)
No notification
2 user interfaces: When using 2 user interfaces, one must be set to "MAIN" and
the other to "SUB".
C2/—
External static pressure
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
M
10(20)
(1)
40
50
60
70
80
90
100
110
120
130
140
150
160
180
200
ThenFN
C1/SW
C2/—
0
01
02
3
02
FDA125A5VEB