Make the following field settings so that they correspond with the actual
installation setup and with the needs of the user:
External static pressure setting using:
-
Airflow automatic adjustment setting
-
User interface
Time to clean air filter
To set airflow automatic adjustment
When the air conditioning unit is running in fan operation mode:
1 Stop the air conditioning unit.
2 Set value number / second code number to 03.
Setting content:
Airflow adjustment is OFF
Press ON/OFF to return to normal operating mode.
Possible consequence: The operation lamp will light up
and the unit will start the fan operation for airflow
automatic adjustment.
Operation stops after 1 to 8 minutes.
Possible consequence: Setting is finished and the
operation lamp will be off.
If there is no change after airflow adjustment, perform the setting again.
INFORMATION
The fan speed of the indoor unit is preset to ensure the standard external static
pressure.
To set a higher or lower external static pressure, reset the initial setting with the
user interface.
User interface
Check the indoor unit setting: the value number / second code number of mode
11(21) must be set to 01.
Change the value number / second code number according to the external static
pressure of the duct to be connected as in table below.
20
Configuration
|
(1)
Then
M
C1/SW C2/—
11(21)
7
01
03
02
Installer and user reference guide