19
Automatic
battery tests
period
20
Battery
maximum
discharge
time setting
21
Ext. Bat
Type
22
Restore de-
fault setting
Set the automatic battery tests
period. Setting range is from 0
to 45days and the default value
is 7days.
0~999: Set the maximum dis-
charge time from 0 to 999min-
utes.UPS will shut down to
protect battery after discharge
time arrives. The default value is
999min.
DIS: Disable battery discharge
protection and backup time will
depend on battery capacity.
STD: The battery type is stand-
ard.UPS will calculate battery
capacity and discharge time.(de-
fault)
CUS: The battery type is cus-
tomed.UPS can't calculate bat-
tery capacity and discharge time.
NO: Not restore default setting
for the UPS.(default)
YES: Restore default setting for
the UPS.UPS need shut down.