03
ECO
mode*
04
Bypass
output
16
0%: ECO mode disabled. When
selected, ECO mode is not
allowed(default)
10%:
ECO mode enabled. When
selected, ECO mode is
activated when the input
voltage is within +/-10% of
setting output voltage
15%:
ECO mode enabled. When
selected, ECO mode is
activated when the input
voltage is within +/-15% of
setting output voltage
Bypass output disabled.
DIS:
When
selected,
output is not allowed in
standby mode. But auto-
matic bypass is acceptable
when overload or other
fault occurs
ENA:
Bypass output enabled.
When
selected,
output is activated when
the utility power is avail-
able even not turn on the
UPS(default)
Bypass
Bypass