15
Short circuit
restart
16
Bypass
voltage
range
17
Bypass
frequency
range
18
ECO
frequency
range
20
ENA:
Short circuit restart ena-
bled. If selected, UPS will
auto restart after short cir-
cuit fault.
DIS:
Short circuit restart disa-
bled. If selected, UPS will
not auto restart after short
circuit fault. (default)
Left parameter: Set the accept-
able low voltage for bypass. Set-
ting range is 10%/15%/20% of
normal output voltage and the
default value is 15%.
Right parameter: Set the accept-
able high voltage for bypass. Set-
ting range is 10%/15% of normal
output voltage and the default
value is 10%.
Set the acceptable frequency
range for bypass. Setting range is
from 1% to 10% of normal out-
put frequency and the default
value is 10%.
Set the acceptable frequency
range for ECO mode. Setting
range is from 1% to 10% of nor-
mal output frequency and the
default value is 5%.