Power cables

1.
All cable screens are connected. Please take the photo and send back.
2.
Grounding cables of transformer, converter and motor are connected
and tightened.
3.
Types and cross sections of power cables are selected according to the
"ABB power cable specification". Cable type
4.
Transformer and motor cables are not fastened at both ends (cables and
converter must be meggered before connection).

Insulation tests

1.
All power cables to drive, and from drive to motor are meggered, and
measured values are within the required limits.
2.
Test report of the megger test available
Note: If the test is carried out by the commissioning engineer of the
drive, an additional day per drive motor combination needs to be
reserved. After the test, the feeder cables can be connected, except at the
drive end. The test must comply with the specification.
3.
Optional insulation tests of the drive are completed and documented.
Insulation tests of the drive recommended in case: long storage time (>4
months), humid environment or visible damages due to
transportation/installation.

Power supply

1.
Medium voltage available for start-up of drive.
2.
Low voltage auxiliary power available for start-up of drive.

Miscellaneous

1.
Sufficient number and correct type of spare parts available .
2.
Cooling of drive room ready for load run of drive.