Signals (Output Signals); Status Signals Via Output Contacts (Digital Outputs); Assignment Of Outputs; Coding The Outputs - AUMA SAEx 25.1 Operation Manual

Multi-turn actuators
Hide thumbs Also See for SAEx 25.1:
Table of Contents

Advertisement

Signals (output signals)

8.
Signals (output signals)
8.1.

Status signals via output contacts (digital outputs)

Characteristics
8.1.1.

Assignment of outputs

8.1.2.

Coding the outputs

8.2.

Analog signals (analog outputs)

Valve position
Torque feedback
58
Output contacts are used to send status signals (e.g. reaching the end positions,
selector switch position, faults...) as binary signals to the control room.
Status signals only have two states: active or inactive. Active means that the
conditions for the signal are fulfilled.
The output contacts (outputs DOUT 1
Required user level: Specialist (4) or higher.
Device configuration M0053
I/O interface M0139
Digital outputs M0110
Signal DOUT 1 M0109
Table 24: Default values
Output
Default value:
Signal DOUT 1
Fault
Signal DOUT 2
End position CLOSED
Signal DOUT 3
End position OPEN
Signal DOUT 4
Selector sw. REMOTE
Signal DOUT 5
Torque fault CLOSE
Signal DOUT 6
Torque fault OPEN
The output signals Coding DOUT 1
active or low active.
High active = output contact closed = signal active
Low active = output contact open = signal active
Signal active means that the conditions for the signal are fulfilled.
Required user level Specialist (4) or higher.
Device configuration M0053
I/O interface M0139
Digital outputs M0110
Coding DOUT 1 M0102
Default values:
Coding DOUT 1 = Low active
Coding DOUT 2
Coding DOUT 12 = High active
Signal: E2 = 0/4
20 mA (galvanically isolated)
Designation in the wiring diagram: AOUT1 (position)
Signal: E6 = 0/4
20 mA (galvanically isolated)
Designation in the wiring diagram: AOUT2 (Torque)
For further information on this topic, please refer to Manual (Operation and setting).
SAEx 25.1
SAEx 30.1 / SAREx 25.1
12) can be assigned to various signals.
Output
Signal DOUT 7
Signal DOUT 8
Signal DOUT 9
Signal DOUT 10
Signal DOUT 11
Signal DOUT 12
Coding DOUT 12 can be set either to high
SAREx 30.1
ACExC 01.2
Default value:
Thermal fault
OPEN
Limit switch CLOSED
Limit switch OPEN
Torque sw. CLOSED
Torque sw. OPEN