Siemens SIMATIC ET 200SP Manual page 25

Analog input module ai 8xi 2-/4-wire ba
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

Errors/accuracies
Linearity error (in relation to input range), (+/-)
Temperature error (in relation to input range), (+/-) 0.005%/K
Crosstalk between inputs, min.
Repeat accuracy in settled state at 25 °C (in rela-
tion to input range), (+/-)
Operational limit in the entire temperature range
Current in relation to input range, (+/-)
Basic error limit (operational limit at 25 °C)
Current in relation to input range, (+/-)
Interference voltage suppression for f = n x (f1 +/-
1%), f1 = interference frequency
Series-mode interference (peak of the interference
< rated value of the input range), min.
Isochronous mode
Isochronous mode (application synchronized up to
terminal)
Interrupts/diagnostics/status information
Interrupts
Diagnostic interrupt
Limit interrupt
Diagnostics alarms
Diagnostics
Monitoring of supply voltage
Wire break
Short-circuit
Group error
Overflow/underflow
Diagnostics indicator LED
Monitoring of the supply voltage (PWR LED)
Channel status display
For channel diagnostics
For module diagnostics
Electrical isolation
Electrical isolation of channels
Between the channels
Between the channels and the backplane bus
Between the channels and the supply voltage of
the electronics
Analog input module AI 8xI 2-/4-wire BA (6ES7134-6GF00-0AA1)
Manual, 03/2015, A5E34941201-AA
Technical specifications
6.1 Technical specifications
6ES7134-6GF00-0AA1
± 0.01%
50 dB
± 0.05%
± 0.5%
± 0.3%
70 dB; with conversion time 67.5 / 22.5 / 18.75
ms: 40 dB
No
Yes
No
Yes
Yes
Yes; for 4 to 20 mA
Yes; encoder supply to ground; module-based
Yes
Yes
Yes; green LED
Yes; green LED
No
Yes; green / red DIAG LED
No
Yes
No
25

Advertisement

Table of Contents
loading