Chapter 4 - Configuration
Function
Prompt
Subnet Mask
Address
Default
Gateway
Shed
Function
Shed Time
Shed SP
Recall
71
Selections or
Range of
Parameter Definition
Setting
55
communication port.
The default value is 10.0.0.2.
0.0.0.0 to
Subnet Mask address, ranging from 0.0.0.0 to
255.255.255.2
255.255.255.255. It only applies to Ethernet
55
communication port.
The default value is 255.255.255.255.
Default Gateway, ranging from 0.0.0.0 to
0.0.0.0 to
255.255.255.255. It only applies to Ethernet
255.255.255.2
communication port.
55
The default value is 0.0.0.0.
Disable
Disables/enables shed functionality. 
Enable
0 to 255
Shed Time —The number that represents how many
sample periods there will be before the controller
sheds from communications. Each period equals 1/3
seconds; 0 equals No shed.
Shed Setpoint Recall
To Local SP
Controller will use last local setpoint.
To Computer
When in "slave" mode, the controller will store the last
SP
host computer setpoint and use it at the Local
setpoint. When in "monitor" mode, the controller will
shed to the last instrument Local or Remote setpoint
used, and the LSP is unchanged.
NOTE: Shed Time is not configurable if
Communication Type is set to Modbus, and
Shed Function is set to Disable.
NOTE: It is not configurable if Shed Function is
set as Disable.