Minimum and Maximum Range Values

Select the Range Values
Calibrate the controller for the minimum (0 %) and maximum
(100 %) range values of your particular input type.
Select the Voltage, Current or Resistance equivalents for 0 % and
100 % range values from
Resistance Equivalents for Input 1 Range
when calibrating your controller.
Table 6-1: Voltage, Milliamp and Resistance Equivalents for Input 1 Range Values
Sensor Type
Thermocouples (per ITS-90)
TC B
TC E High
TC E Low
TC J High
TC J Mid
TC J Low
TC K High
TC K Mid
TC K Low
Table 5-1  Voltage, Milliamp and
Values-. Use these values
PV Input
Range
°F
°C
0 to
–18 to
3300
1816
–454
–270
to
to
1832
1000
-200
-129
to
to 593
1100
0 to
–18 to
1600
871
20 to
–7  to
900
482
20 to
–7 to
550
288
0 to
–18 to
2400
1316
–20 to
–29 to
1200
649
–20 to –29 to
Chapter 6 -  Input Calibration
Range Values
0%
100%
–0.100
13.769 mV
mV
–9.835
76.373 mV
mV
–6.472
44.555 mV
mV
–0.886
50.060 mV
mV
– 0.334
26.400 mV
mV
–0.334
15.650 mV
mV
–0.692
52.952 mV
mV
–1.114
26.978 mV
mV
–1.114
16.350 mV