The operator panel is connected to the last function module that is actually available for
IO-Link.
If there are gaps in the configuration because a function module is missing, they can be
bridged with a long 14-pin module connector.
• 90 mm (3RA2711‑0EE06)
• 260 mm (3RA2711‑0EE07)
• 335 mm (3RA2711‑0EE08)
View
Gap (function module for IO-Link not present)
Module connector, 14‑pin, length 90 mm, 260 mm or 335 mm
IO-Link
Auxiliary voltage V
Maximum 1 m
Figure 7-1
Configuration with parameter "Starter available" = no
Exception
2 consecutive empty slots for 2 star-delta starters are not allowed.
7.1.3
Parameter "Operation at Preset <> Actual Operation"
Parameter "Operation at Preset <> Actual Operation"
The "Operation at Preset <> Actual Operation" parameter determines whether or not the types
of starter of the ACTUAL configuration are to be compared with those of the PRESET
configuration.
SIRIUS 3RA2711 function modules for IO-Link
Equipment Manual, 08/2022, A8E96801709001A/RS-AD/006
Aux
Parameters
7.1 Parameters for starters 1 to 4
61