Operator Control; Settings On The Function Modules For Io-Link - Siemens SIRIUS 3RA2711 Equipment Manual

Industrial switchgear
Table of Contents

Advertisement

Operator control

11.1

Settings on the function modules for IO-Link

Direct and reversing starters
No settings are necessary on direct and reversing starters before commissioning.
Star-delta starter
On the IO-Link basic module for star-delta starting, use the setting controller to set the startup
time in star mode. You can select a startup time between 3 and 60 seconds. After expiry of the
startup time, the basic module switches to delta mode.
The switchover time from star mode to delta mode is at least 50 ms.
Startup time in star mode
Switchover time from star mode to delta mode
Figure 11-1
Setting the switchover time from star mode to delta mode
SIRIUS 3RA2711 function modules for IO-Link
Equipment Manual, 08/2022, A8E96801709001A/RS-AD/006
11
91