Operator control
11.1
Settings on the function modules for IO-Link
Direct and reversing starters
No settings are necessary on direct and reversing starters before commissioning.
Star-delta starter
On the IO-Link basic module for star-delta starting, use the setting controller to set the startup
time in star mode. You can select a startup time between 3 and 60 seconds. After expiry of the
startup time, the basic module switches to delta mode.
The switchover time from star mode to delta mode is at least 50 ms.
①
Startup time in star mode
②
Switchover time from star mode to delta mode
Figure 11-1
Setting the switchover time from star mode to delta mode
SIRIUS 3RA2711 function modules for IO-Link
Equipment Manual, 08/2022, A8E96801709001A/RS-AD/006