Superheat controller, Type EKE 1A, 1B, 1C, 1D
Table 47: Manual control of Relay:
Parameter
Function
O018
Manual mode
B101
Manual mode timeout
B103
Manual relay DO1
When DI2 /DI 3 is configured as Preset OD, the valve OD will be positioned as defined by valve OD parameter [I078 -
Preset OD].
Table 48: Manual Control Valve:
Parameter
Function
O018
Manual mode
B101
Manual mode timeout
O045
Manual OD
Used to calibrate the valve at Zero OD %. When the user set the manual homing, a full closing operation will be
performed (same as initial closing). After the operation is performed the manual homing parameter [B104 - Manual
Homing] will be set back to off and the parameter for [O045 Manual OD] will be set to 0%. When manual mode
becomes inactive the actual OD will be the starting point for automatic control
Table 49: Manual Homing:
Parameter
Function
O018
Manual mode
B101
Manual mode timeout
O045
Manual OD
Figure 84: Switching between Auto and manual mode
Auto control
Manual mode ON

6.3.4 Valve configuration

Table 50: Valve Configuration
Parameter
Function
I067
Valve Configuration
I067
User Defined valve
© Danfoss | Climate Solutions | 2022.06
Description
1 = On
time in sec. When timed out the parameter [O018 - Manual Mode] will be set to of
0 = Off | 1 = ON
Description
1 = On
time in sec. When timed out the parameter [O018 - Manual Mode] will be set to Off
Set desired OD in Percentage %
Description
1 = On
time in sec. When timed out the parameter [O018 - Manual Mode] will be set to Off
Set desired OD in Percentage %
Auto control
Time
Description
Danfoss stepper motor are easily selected from Valve configuration list. On selecting the valve, the
controller will automatically load pre-defined default values. The user is not required to set other
stepper motor parameters for a selected valve from the valve configuration list.
 NOTE:
I028 parameter (Valve drive current) needs to be adjusted if the chosen cable length is between
15 and 30m, refer to the installation section
If a valve from other manufacturers is used, such valve can be defined as
1.
Set I067 to ''User defined Valve''
2.
Enter the Valve parameters (Parameters described below).
BC398828796060en-000101 | 58