Danfoss EKE 1A User Manual page 48

Superheat controller
Hide thumbs Also See for EKE 1A:
Table of Contents

Advertisement

Superheat controller, Type EKE 1A, 1B, 1C, 1D
Figure 70: Offsetting Superheat, Temperature and OD Via External signal
Offset
R006
Ext. ref offset max.
5
R106
Ext. ref offset min
0
I034
Ext ref. voltage low
 NOTE:
Offset can be done in positive and negative direction. Extra care must be taken while doing this setting.
Table 30: Offsetting references for EKE 1A
Parameter
Function
I021
AI4 Configuration
R106
Ext. ref offset min.
R006
Ext. ref offset max
O089
Ext ref. supply
I034
Ext ref voltage low
I035
Ext ref. voltage high
Table 31: Offsetting references for EKE 1B, 1D
Parameter
Function
I021
AI4 Configuration
R106
Ext. ref offset min.
R006
Ext. ref offset max
O089
Ext ref. supply
I034
Ext ref voltage low
I035
Ext ref. voltage high
I036
Ext ref. current low
I037
Ext ref. current high
X010
Bus ext. ref
Table 32: Offsetting parameters EKE 1C
Parameter
Function
I021
AI4 Configuration
R106
Ext. ref offset min.
R006
Ext. ref offset max
© Danfoss | Climate Solutions | 2022.06
R006
Ext. ref offset max.
Voltage
10
I035
R106
Ext ref. voltage high
Ext. ref offset min
Description
Ext. reference
This setting determines how large the offset is when input signal is at min.
This setting determines how large the offset is when input signal is at max.
Define how the external reference signal is used
0 = V->SH: Displacement of SH reference given by External voltage signal.
1 = V->Temp: Displacement of temperature given External voltage signal.
Define min. reference Voltage
Define max. reference Voltage
Description
Ext. reference
This setting determines how large the offset is when input signal is at min.
This setting determines how large the offset is when input signal is at max.
Define how the external reference signal is used
1 = V->SH: Displacement of SH reference given by External voltage signal.
3 = V->Temp: Displacement of temperature given External voltage signal.
4 = Bus -> SH: Displacement of SH reference given via Modbus.
6 = Bus -> T: Displacement of temperature given via Modbus
Define min. reference Voltage
Define max. reference Voltage
Define min. reference current
Define max. reference current
Readout offset in Kelvin
Description
Ext. reference
This setting determines how large the offset is when input signal is at min.
This setting determines how large the offset is when input signal is at max.
Offset
4
I036
Ext ref. current low
4
-2
Ext ref. current hig h
BC398828796060en-000101 | 48
Current
20
I037

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Eke 1bEke 1cEke 1d