Devices Required For Connection - Omron SYSMAC CS1W-CLK13 Operation Manual

Optical ring controller link units, h-pcf/gi cable
Table of Contents

Advertisement

Specifications and Configurations
CS1W-CLK52 Optical Ring
Controller Link Unit
Name
CPU Backplane (8 slots)
CPU Unit
Controller Link Unit (Optical)
Total
1-2-6

Devices Required for Connection

Communications Cables
Optical Bus or Optical
Ring System (H-PCF
Cable)
Install the Controller Link Unit onto a CPU Backplane or CS-series Expansion
Backplane. (The Controller Link Unit is classified as a CPU Bus Unit.)
4 maximum including other types
of Controller Link Units
CPU
Unit
CPU Backplane
3/5/10 slots
Of these 14, 16, or
21 slots, installa-
tion is possible in
up to 4 slots.
Expansion CPU
Backplane
11 slots
Up to eight CS-series Controller Link Units with unit version 1.2 or later can be
connected to a single CPU Unit. When connecting multiple Controller Link
Units to the CPU Unit, consider the current consumption of the CPU Unit and
each CPU Bus Unit before selecting the Power Supply Unit. For details on
Controller Link Unit current consumption, refer to Controller Link Unit Models
and PLCs on page 17. For details on current consumption of each Unit, refer
to the SYSMAC CS Series Programmable Controllers Operation Manual
(W339).
The following table provides an example of current consumption
Example: Using the C200HW-PA209R Power Supply Unit supplying a maxi-
mum current of 9.0 A (5 V) and maximum power of 45 W.
Model
Current consumption
CS1W-BC083
0.11 A
CS1H-CPU67H
0.82 A
CS1W-CLK52-V1 0.65 A
To set up a Controller Link Network the following devices are needed in addi-
tion to a Controller Link Unit and a PLC.
The following devices are required for the Optical Bus or Optical Ring (H-PCF)
Controller Link Network. The cable and connectors are the same as those
used for Optical SYSMAC LINK Networks.
Number of
per Unit (A)
Units
1
1
8
Section 1-2
Current consumption
(A)
0.11 A
0.82 A
5.20 A
6.13 (power consump-
tion: 30.65 W)
21

Advertisement

Table of Contents
loading

Table of Contents