Please ensure item code 105 is set to "1" on the QAHV before proceeding
Touch [Initial Settings] in the menu bar, and then touch [HW Supply].
Set the address, group names, and detail settings for each group of HWHP (QAHV) unit that is connected to
the AE-200/ EW-50. Touch [Save Settings] when done
1. Detail settings for HWHP (QAHV) units
In the [HW Supply] screen, touch the "Detail settings" button.
The detail settings window will appear.
Note: Only the "Detail settings" buttons for the HW Supply groups whose initial startup
procedure have been completed are available for selection
2. Set the settings that are related to operation modes under "Mode setting."
Set the number corresponding to the sensor to be used to determine the "Thermo-ON" status
under "Operation ON sensor."
Set the number corresponding to the sensor to be used to determine the "Thermo-OFF" status
under "Operation OFF sensor."
Set "Operation ON differential" to a temperature between 0.5ºC (1ºF) and 23.0ºC (46ºF).
Units will start operating when the differential between the set temperature and the temperature
setting for "Operation ON sensor" exceeds the value set for "Operation ON
differential."

20. AE200

46