Section: Installation
6.10 Relief Valve
Ensure that the pressure relief valve is installed with no valves or other means of isolation
between its inlet and the boiler.
Make sure the relief valve outlet is piped with unobstructed piping (minmum 3/4" diameter) to a
safe discharge location.
6.10.1 Pressure Gauge
The boiler does not include a water pressure sensor. Field piping should always include a water
pressure gauge or a tridicator.
26