10.2 Replacing the elements

Heating elements come in sizes 2kW for the EBX4K-240, 4kW for the EBX8K-240, 5kW for the
EBX10K-240, and 6kW for the EBX12K-240. The elements can be replaced only by models of
identical wattage.
Figure 23
Element hex heads
1. Power off boiler and open cabinet door.
2. Close the water isolation valves and drain the boiler.
3. Remove and set aside the four screws of the cabinet lid. Remove the cabinet lid.
4. Label the element wires and disconnect them.
5. Unscrew the elements from the heat exchanger and lift straight upwards to remove.
6. Reassemble in reverse order.
Section: Service and maintenance
Figure 24
Unscrew and lift out elements