Siemens SITRANS LG270 Operating Instructions Manual page 36

Profibus pa rod and cable probe
Table of Contents

Advertisement

Max. adjustment interface
Min. adjustment interface
36
Adjust the requested percentage value with [+] and store with [OK].
Enter the suitable distance value in m for the empty vessel (e.g.
distance from the flange to the probe end) corresponding to the per-
centage value. The distance refers tot he sensor reference plane (seal
surface of the process fitting).
This menu item is only available if you have selected interface meas-
urement under the menu item "Application".
Enter the requested percentage value for the max. adjustment.
As an alternative, you have the possibility taking over the adjustment
of the level measurement also for the interface.
Enter the respective distance value in m for the surface of the upper
medium corresponding to the percentage value.
This menu item is only available if you have selected interface meas-
urement under the menu item "Application".
Enter the requested percentage value for the min. adjustment (inter-
face).
Enter the respective distance value in m for the interface correspond-
ing to the percentage value of the interface.
SITRANS LG270 - Operating Instructions
PBD-51041506