Mounting Instructions - Siemens SITRANS LG270 Operating Instructions Manual

Profibus pa rod and cable probe
Table of Contents

Advertisement

Installation position
14
the process conditions in chapter "Technical data" of the operating
instructions or on the type label.
Hence make sure before mounting that all parts of the instrument ex-
posed to the process are suitable for the existing process conditions.
These are mainly:
Active measuring component
Process fitting
Process seal
Process conditions in particular are:
Process pressure
Process temperature
Chemical properties of the medium
Abrasion and mechanical influences
4.2

Mounting instructions

Mount SITRANS LG270 in such a way that the distance to vessel
installations or to the vessel wall is at least 300 mm (12 in). In non-
metallic vessels, the distance to the vessel wall should be at least
500 mm (19.7 in).
During operation, the probe must not touch any installations or the
vessel wall. If necessary, fasten the probe end.
In vessels with conical bottom it can be advantageous to mount the
sensor in the center of the vessel, as measurement is then possible
nearly down to the lowest point of the bottom. Keep in mind that
measurement all the way down to the tip of the probe may not be pos-
sible. The exact value of the min. distance (lower dead zone) is stated
in chapter "Technical data".
Fig. 4: Vessel with conical bottom
SITRANS LG270 - Operating Instructions
PBD-51041506