MI 3152(H) EurotestXC (2,5 kV)
High resistance to earth of current test probes. Results may be impaired.
High resistance to earth of potential test probes. Results may be impaired.
High resistance to earth of potential and current test probes. Results may be
impaired.
Too small current for declared accuracy. Results may be impaired. Check in
Current Clamp Settings if sensitivity of current clamp can be increased.
In Earth 2 Clamp measurement results are very accurate for resistances
below 10 Ω. At higher values (several 10 Ω) the test current drops to few mA.
The measuring accuracy for small currents and immunity against noise
currents must be considered!
Measured signal is out of range (clipped). Results are impaired.
Single fault condition in IT system. (MI 3152 only)
Fuse F1 is broken.
3.4.5

Result indication

Measurement result is inside the set limits (PASS).
Measurement result is outside the set limits (FAIL).
Measurement is aborted. Consider displayed warnings and messages.
3.4.6
Auto Sequence® result indication
All Auto Sequence® results or single tests with the
set limits are inside the set limits (PASS).
At least one Auto Sequence® single test result with
the set limits is outside the set limits (FAIL).
All applied single tests in the Auto Sequence® are
without the set limits and results without PASS /
FAIL indication.