Water pre-heating coil
Like the electric pre-heating coil, a hot water pre-heating coil can be provided. The control system is tripped automatically when the
outdoor air temperature drops below -10 °C, modulating the 3-way valve of the coil to increase the air temperature up to 5 °C.
Water post-heating coil
Like the electric post-heating coil, a water post-heating coil can be provided that can bring the delivery temperature back to the values
required for comfort indoors. A 3-way modulating valve controls the power supplied by the post-heating coil.
Like the electric post-heating coil, the water post-heating coil can be used in the winter to compensate for the defrost cycles of the
outdoor units, or in the summer, only for the B-OU version, to compensate for forced dehumidification when this is required.
H
O post-heating coil
2
Size of unit
WIZARDX 3000
WIZARDX 5000
WIZARDX 7500
WIZARDX 10000
WIZARDX 12500
WIZARDX 15000
WIZARDX 20000
MODEL
3000 5000 7500 10000 12500 15000 20000
H
O pre-heating coil
14
2
Size of unit
WIZARDX 3000
WIZARDX 5000
WIZARDX 7500
WIZARDX 10000
WIZARDX 12500
WIZARDX 15000
WIZARDX 20000
MODEL
3000
14
Pre-heating
ΔP [kPa]
P [kW]
Q [l/h]
5.14
979
28.20
8.56
1631
23.20
12.84
2447
23.10
17.12
3262
13.60
21.40
4078
22.10
25.68
4893
22.00
34.24
6524
29.40
AIR
IN: -15°C OUT: -10°C
WATER IN: 45°C
OUT:40°C
Weight [kg]
20
24
32
36
Post-heating
ΔP [kPa]
P [kW]
Q [l/h]
5.22
898
17.00
8.71
1497
14.10
13.06
2246
14.00
17.41
2995
8.30
21.77
3744
13.40
26.12
4492
13.30
34.83
5990
17.70
AIR
IN: 16°C OUT:21°C
WATER IN: 45°C OUT:40°C
Weight [kg]
5000
7500
10000
12500
20
24
32
36
IUM_WIZARDX_03_22_EN
42
56
15000
20000
42
56
76