Mitsubishi Electric WIZARDX Instructions For Installation, Use And Maintenance Manual page 37

Air-handling units
Table of Contents

Advertisement

2.2.2.2
Joining the sections
The procedure for joining the sections of a unit after lifting is as follows:
1.
Check that the order of the sections is exactly the same as shown in the technical drawing supplied.
2.
Check that the side with the connectors and inspection doors of the sections is exactly the same as the one shown in
the drawing.
3.
The material for joining the sections is supplied in a box inside the delivery fan section or in the filter access plenums
(for small machines).
4.
Before joining the sections:
o
clean the section bars and apply the supplied self-adhesive gasket;
o
waterproof the area where the individual modules are coupled together using silicone sealant (fig.A);
o
por units equipped with a weather cover panel, before joining the modules together, apply silicone to the
edges of the canopy at the joints, so as to increase the seal of the cover itself (fig.C).
5.
Put the sections together, verifying the perfect alignment and planarity of the parts.
6.
Join the sections with the brackets provided, arranging them as shown on the attached drawing in the fan chamber and
according to the required configuration of the unit.
7.
After assembly, seal the spaces between the individual modules using the silicone provided (fig. B).
IUM_WIZARDX_03_22_EN