Replacement of the PAC-IF interface cards
C-OU version
If the card is faulty and needs to be replaced, make all the electrical connections as on the original card.
Make sure to also set the DIP SWITCHES on the new PAC-IF interface card as illustrated below.
The DIP SWITCHES of the SW1, SW2, SW3, SW6 must be set in the same way for all the PAC-IF interface cards in the switchboard
of the WIZARDX unit.
INFORMATION:
The DIP SWITCH SW1-7 must be set at:
OFF if control is on the supply line
ON if control is on the return line
IUM_WIZARDX_03_22_EN
72