Implement the following measures:
1.
handle the unit at an ambient temperature above -10°C and when there is no wind;
2.
make sure that no unit components are damaged and that they are correctly installed;
3.
use all, and only, the lifting points indicated in the dimensional drawing and marked on the unit;
4.
use cables of suitable load-bearing capacity and length, as indicated in the dimensional drawing;
5.
make sure that the ropes are securely attached to the unit using suitable devices;
6.
it is obligatory to use a sling bar of suitable weight-bearing capacity to guarantee stability when lifting and to prevent the
cables from coming in contact with the unit;
7.
make sure that the lifting ropes will not damage the machine during lifting.
If it is not possible to keep the ropes away from the unit, place appropriate protection materials between the two;
8.
move the machine carefully and avoid abrupt movements;
9.
keep at a safe distance and do not, for any reason, stand with parts of the body under or near the lifted unit;
10. move the unit carefully and avoid abrupt movements. Do not tilt the machine more than 6° during handling;
11. keep at a safe distance and do not, for any reason, stand with parts of the body under or near the lifted unit.
The surface on which the unit is placed must be level and sufficiently strong to take the weight of the machine when full of water and
running, as indicated in the dimensional drawing.
To reduce vibrations to the supporting structures, assemble vibration dampers at each fastening point indicated in the dimensional
drawing.
Install the vibration dampers under the base with the unit lifted no more than 200 mm off the ground and avoid standing with parts of
the body under the unit.
In any case, always secure the unit on the support base. The vibration dampers may extend outside the span of the machine and,
in which case, will require suitable support.
In the case of installation on a raised surface, make sure that the handle of the power disconnector is easy to access and at a height
of between 0.6m and 1.9m above the floor (EN60204-1).
IUM_WIZARDX_03_22_EN
31