CAUTION:
Correct installation of the machine requires compliance with the clearances shown in the figure (plan view of an
example of a WIZARDX unit). This allows ease of access to the components of the machine for the purpose of normal
inspection and maintenance operations.
The unit must be put in a position where there is sufficient space for performing routine and extraordinary maintenance. Observe the
following points:
- W: width of the WIZARDX unit;
- A: arrange for an area in front of the side of the inspection doors and manifolds that is as long as the machine and of a width of 800
mm;
- B: arrange for an area in front of the side opposite that of the connectors and inspection doors, as long as the machine and of a
width equal to the width of the AHU (W) plus 200 mm, so that the coils can be taken out without the need to remove the cooling
circuits or valve assemblies. If this area cannot be arranged here (for example if the unit is near a wall), it must instead be arranged
in front of the side of the inspection doors and manifolds.
- C: arrange for an area at the point of the air outlet and air inlet of a width equal to the width of the AHU (W) and of a length of 1000
mm.
INFORMATION:
In the case of accessories and options (for example a humidifier module or a mixing module), the clearances must be
calculated considering the maximum overall dimensions with all the accessories/options provided.
Check the dimensions of the accessories/options in the relevant chapter.