See the illustrative diagram below (for making actual connections, refer to the wiring diagram on the machine). In the legend, the
number of the circuit is indicated with "#".
Legend:
"#"TH2: thermistor for the temperature of the refrigerant in its liquid state. It is located in the relative probe sump welded on
the distributor of the exchanger
"#"TH5: thermistor for the temperature of the refrigerant in its two-phase state. It is located in the relative probe sump welded
in an appropriate position on the circuit
"#"S2: signal connection between the PAC-IF interface card and the Mr. Slim condenser
"#"S3: signal connection between the PAC-IF interface card and the Mr. Slim condenser
"#"G: line of the refrigerant in its gaseous state
"#"L: line of the refrigerant in its liquid state
: direct expansion coil
The WIZARDX unit is delivered with the TH2 and TH5 thermistors, which are required for correct operation of the unit, already in
their probe sumps. It is forbidden to change the position the thermistors as to do so could affect correct operation and safety of the
unit.