SiUS122226E
1.1.3 Duct Concealed Type
Model
Power Supply
Rated Capacity
Casing Color
Dimensions (H × W × D)
Coil
Type
Rows × Stages × Fin per Inch
Face Area
Fan
Type
Motor Output
Airflow Rate
H / M / L
External Static
Pressure 1
Sound Pressure Level
Sound Power Level
Air Filter 2
Weight (Mass)
Piping
Liquid
Connection
Gas
Drain
Remote
Wired
Controller
Wireless
(Option)
Drawing No.
Notes
Model
Power Supply
Rated Capacity
Casing Color
Dimensions (H × W × D)
Coil
Type
Rows × Stages × Fin per Inch
Face Area
Fan
Type
Motor Output
Airflow Rate
H / M / L
External Static
Pressure 1
Sound Pressure Level
Sound Power Level
Air Filter 2
Weight (Mass)
Piping
Liquid
Connection
Gas
Drain
Remote
Wired
Controller
Wireless
(Option)
Drawing No.
Notes
Conversion Formulae
kcal/h = kW × 860
Btu/h = kW × 3412
cfm = m³/min × 35.3
Part 2 Specifications
CDMQ07WVJU9
Cooling
Phase
Hz, V
60 Hz, 208 - 230 V
7 kBtu/h Class
in. (mm)
9-5/8 × 27-9/16 × 31-1/2 (245 × 700 × 800)
Cross Fin Coil
3 × 26 × 18
ft² (m²)
1-15/16 (0.178)
Sirocco Fan
HP
cfm
268 / 251 / 230
(m³/min)
(7.6 / 7.1 / 6.5)
inH
O
0.20 (0.60 - 0.12)
2
Pa
50 (150 - 30)
dB(A)
30
dB(A)
44
lbs (kg)
64 (29)
1/4 (6.4) (Flare)
in. (mm)
3/8 (9.5) (Flare)
in. (mm)
I.D. 1 (25) / O.D. 1-1/4 (32)
in. (mm)
BRC1E73
BRC082A43
3D141740A
1. External static pressure is changeable in 13 stages by
remote controller. Refer to page 260 for details.
2. Air filter is not standard accessory, but please mount it
in the duct system of the suction side.
Select its dust collection efficiency (gravity method) 50% or
more.
FDMQ12WVJU9
Cooling
Phase
Hz, V
60 Hz, 208 - 230 V
12 kBtu/h Class
in. (mm)
9-5/8 × 27-9/16 × 31-1/2 (245 × 700 × 800)
Cross Fin Coil
3 × 26 × 18
ft² (m²)
1-15/16 (0.178)
Sirocco Fan
HP
cfm
371 / 318 / 261
(m³/min)
(10.5 / 9.0 / 7.4)
inH
O
0.20 (0.60 - 0.12)
2
Pa
50 (150 - 30)
dB(A)
33
dB(A)
47
lbs (kg)
64 (29)
1/4 (6.4) (Flare)
in. (mm)
3/8 (9.5) (Flare)
in. (mm)
I.D. 1 (25) / O.D. 1-1/4 (32)
in. (mm)
BRC1E73
BRC082A43
3D143150
1. External static pressure is changeable in 13 stages by
remote controller. Refer to page 260 for details.
2. Air filter is not standard accessory, but please mount it
in the duct system of the suction side.
Select its dust collection efficiency (gravity method) 50% or
more.
Heating
1
—
0.17
268 / 251 / 230
(7.6 / 7.1 / 6.5)
30
44
—
1. External static pressure is changeable in 13 stages by
remote controller. Refer to page 260 for details.
2. Air filter is not standard accessory, but please mount it
in the duct system of the suction side.
Select its dust collection efficiency (gravity method) 50% or
more.
Heating
1
—
0.17
371 / 318 / 261
(10.5 / 9.0 / 7.4)
33
47
—
1. External static pressure is changeable in 11 stages by
remote controller. Refer to page 260 for details.
2. Air filter is not standard accessory, but please mount it
in the duct system of the suction side.
Select its dust collection efficiency (gravity method) 50% or
more.
Specifications
FDMQ09WVJU9
Cooling
Heating
1
60 Hz, 208 - 230 V
9 kBtu/h Class
—
9-5/8 × 27-9/16 × 31-1/2 (245 × 700 × 800)
Cross Fin Coil
3 × 26 × 18
1-15/16 (0.178)
Sirocco Fan
0.17
293 / 265 / 233
293 / 265 / 233
(8.3 / 7.5 / 6.6)
(8.3 / 7.5 / 6.6)
0.20 (0.60 - 0.12)
50 (150 - 30)
32
32
46
46
—
64 (29)
1/4 (6.4) (Flare)
3/8 (9.5) (Flare)
I.D. 1 (25) / O.D. 1-1/4 (32)
BRC1E73
BRC082A43
3D143150
FDMQ15WVJU9
Cooling
Heating
1
60 Hz, 208 - 230 V
15 kBtu/h Class
—
9-5/8 × 39-3/8 × 31-1/2 (245 × 1,000 × 800)
Cross Fin Coil
2 × 26 × 18
3-1/8 (0.288)
Sirocco Fan
0.31
448 / 399 / 350
448 / 399 / 350
(12.7 / 11.3 / 9.9)
(12.7 / 11.3 / 9.9)
0.20 (0.60 - 0.20)
50 (150 - 50)
34
34
48
48
—
77 (35)
1/4 (6.4) (Flare)
1/2 (12.7) (Flare)
I.D. 1 (25) / O.D. 1-1/4 (32)
BRC1E73
BRC082A43
3D143151
19