7.12 Four Way Valve Abnormality
EA
Error Code
Outdoor Unit LED
A j 1 i 2 h 3 h 4 h 5 h
Display
Method of Error
The liquid pipe thermistor and the outdoor heat exchanger thermistor are checked to see if they
Detection
function within their normal ranges in the operating mode.
Error Decision
The following condition continues for A seconds after the compressor has started.
Conditions
Cooling operation
Heating operation
A (seconds)
Tde: outdoor heat exchanger temperature
Supposed
Disconnection of four way valve coil
Causes
Defective four way valve, coil, or harness
Defective outdoor unit PCB
Defective thermistor
Refrigerant shortage
Water mixed in refrigerant
Defective stop valve
Part 6 Service Diagnosis
The lowest liquid pipe temperature among the rooms in operation –Tde > 45°C (81°F)
The highest liquid pipe temperature among the rooms in operation –Tde < 0°C (0°F)
Cooling
Heating