4.14 Four Way Valve Abnormality
EA
Error Code
The room temperature thermistor and the indoor heat exchanger thermistor are checked if they
Method of Error
function within their normal ranges in each operation mode.
Detection
A following condition continues over 10 minute after operating for 5 minutes.
Error Decision
Conditions
Cooling / Dry
Heating
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 60 minutes without any other error
Disconnection of four way valve coil
Supposed
Defective four way valve, coil, or harness
Causes
Defective outdoor unit PCB
Defective thermistor
Refrigerant shortage
Water mixed in refrigerant
Defective stop valve
Service Diagnosis
A – B < –5°C
B – A < –5°C
A: Room thermistor temperature
B: Indoor heat exchanger temperature
Troubleshooting