SiUS041638EA
4.15 Four Way Valve Abnormality
EA
Error Code
Method of Error
The room temperature thermistor and the indoor heat exchanger thermistor are checked if they
Detection
function within their normal ranges in each operation mode.
Error Decision
The following condition continues over 10 minutes after operating for 5 minutes.
Conditions
Cooling/Dry
Heating
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 60 minutes without any other error
Supposed
Disconnection of four way valve coil
Causes
Defective four way valve, coil, or harness
Defective outdoor unit PCB
Defective thermistor(s)
Refrigerant shortage
Water mixed in refrigerant
Defective stop valve
Service Diagnosis
A – B < –5°C (A – B < –9°F)
B – A < –5°C (B – A < –9°F)
A: Room thermistor temperature
B: Indoor heat exchanger temperature
Troubleshooting
78