Preparing for Installation
This chapter describes how to prepare your site for the Sun Fire 6800, Sun Fire 4810,
Sun Fire 4800, and Sun Fire 3800 systems.
Note – For information about physical specifications, electrical specifications, and
environmental requirements, refer to the Sun Fire 6800/4810/4800/3800 Systems Site
Planning Guide.
Verifying the Electrical
I
Verifying the Air
I
Verifying the Floor
I
1.1
Verifying the Electrical Circuits
Because large AC currents may be needed, each of the following items requires a
separate power circuit:
Each AC power cord for the system (or each RTS power cable for Sun Fire 6800
I
systems and systems mounted in a Sun Fire cabinet)
External peripherals
I
Monitor used for diagnostics
I
The Sun Fire 6800 system requires four dedicated 200–240 VAC, 30A circuit breakers.
Caution – Do not attach other electrical equipment to the AC circuit for the system;
system reliability can be affected.
Circuits—page 1-1