Parameters/address space
4.1 Parameters
The following parameter settings are possible:
Table 4- 1
Configurable parameters and their defaults (GSD file)
Parameters
Diagnostics:
No supply voltage L+
Channel activated
Reaction to CPU
STOP
Potential group
Due to the limited number of parameters at a maximum of 244 bytes per ET 200SP station with a PROFIBUS GSD
1
configuration, the configuration options are restricted. If required, you can assign these parameters using data rec-
ord 128 as described in the "GSD file PROFINET IO" column (see table above). The parameter length of the I/O module
is 6 bytes.
16
Range of values
Disable
•
Enable
•
Disable
•
Enable
•
Turn off
•
Keep last value
•
Output substitute
•
value 1
Use potential group
•
of the left module
(module plugged in-
to a dark-colored
BaseUnit)
Enable new potential
•
group (module
plugged into light-
colored BaseUnit)
Default
Parameter
reassignment
in RUN
Disable
Yes
Enable
Yes
Turn off
Yes
Use po-
No
tential
group of
the left
module
DQ 16x24VDC/0.5A BA digital output module (6ES7132-6BH00-0AA0)
Scope with configuration software, e.g.
STEP 7 (TIA Portal)
GSD file
PROFINET IO
PROFIBUS DP
Module
Module
Channel
Channel
Channel
Module
Module
Module
Manual, 02/2018, A5E42404662-AA
GSD file
1