Parameter Data Record; Parameter Assignment And Structure Of Parameter Data Record - Siemens SIMATIC ET 200SP Manual

Digital output module
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

Parameter data record

A.1

Parameter assignment and structure of parameter data record

The data records of the module have an identical structure, regardless of whether you
configure the module with PROFIBUS DP or PROFINET IO.
Parameter assignment in the user program
You can change the parameters of the module in RUN.
Changing parameters in RUN
The "WRREC" instruction is used to transfer the parameters to the module using data record
128. The parameters set with STEP 7 are not changed in the CPU, which means the
parameters set in STEP 7 will be valid after a restart.
Output parameter STATUS
The module ignores errors that occur during the transfer of parameters with the "WRREC"
instruction and continues operation with the previous parameter assignment. However, a
corresponding error code is written to the STATUS output parameter.
The description of the "WRREC" instruction and the error codes is available in the STEP 7
online help.
DQ 4x24..230VAC/2A ST digital output module (6ES7132-6FD00-0BB1)
Manual, 02/2014, A5E32043575-AA