Declaration Of Parameters - Siemens SIMATIC ET 200SP Manual

Digital output module dq 16x24vdc/0.5a ba
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

4.2

Declaration of parameters

Diagnostics: No supply voltage L+
Enabling of the diagnostics for no or insufficient supply voltage L+.
Channel activated
Determines whether a channel is activated or deactivated.
Reaction to CPU STOP
Determines the behavior of the module in the event of a CPU STOP.
Potential group
A potential group consists of a group of directly adjacent I/O modules within an ET 200SP
station, which are supplied via a common supply voltage.
A potential group begins with a light-colored BaseUnit through which the required voltage is
supplied for all modules of the potential group. The light-colored BaseUnit interrupts the
three self-assembling voltage buses P1, P2 and AUX to the left neighbor.
All additional I/O modules of this potential group are plugged into dark-colored BaseUnits.
You take the potential of the self-assembling voltage buses P1, P2 and AUX from the left
neighbor.
A potential group ends with the dark-colored BaseUnit, which follows a light-colored
BaseUnit or server module in the station configuration.
See also
ET 200SP distributed I/O system
(http://support.automation.siemens.com/WW/view/en/58649293)
DQ 16x24VDC/0.5A BA digital output module (6ES7132-6BH00-0AA0)
Manual, 02/2018, A5E42404662-AA
Parameters/address space
4.2 Declaration of parameters
17

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

6es7132-6bh00-0aa0

Table of Contents