Technical specifications of the DQ 16×24VDC/0.5A BA
Article number
General information
Product type designation
Firmware version
FW update possible
•
usable BaseUnits
Color code for module-specific color identifica-
tion plate
Product function
I&M data
•
Engineering with
STEP 7 TIA Portal configurable/integrated
•
as of version
STEP 7 configurable/integrated as of ver-
•
sion
PROFIBUS as of GSD version/GSD revi-
•
sion
PROFINET as of GSD version/GSD revi-
•
sion
Operating mode
DQ
•
DQ with energy-saving function
•
PWM
•
Oversampling
•
MSO
•
Supply voltage
Rated value (DC)
permissible range, lower limit (DC)
permissible range, upper limit (DC)
Reverse polarity protection
Input current
Current consumption, max.
Output voltage
Rated value (DC)
22
6ES7132-6BH00-0AA0
DQ 16x 24 V DC/0.5 A BA, PU 1
V0.0
No
BU type A0
CC00
Yes; I&M0 to I&M3
V14
STEP 7 V5.5 or higher
One GSD file each, Revision 3 and 5 and higher
GSDML V2.3
Yes
No
No
No
No
24 V
19.2 V
28.8 V
Yes
55 mA; without load
24 V
DQ 16x24VDC/0.5A BA digital output module (6ES7132-6BH00-0AA0)
6