6 Electrical connection

User Manual – JXM-IO-E32
Signal disruption due to incorrect CAN wiring
Unshielded or incorrectly twisted CAN lines may cause com-
munication faults. In the worst case, a malfunction of the de-
vice can lead to subsequent physical injury.
Connect 120 Ω termination resistors to both ends of the
CAN bus.
Alternatively, connect the internal terminating resistor (see
pinout).
Improving electromagnetic compatibility
Improper implementation of the wiring harness may impair
electromagnetic compatibility.
Keep the cables as short as possible.
Lay power lines and signal lines separated from each
other.
Damages to material or functional impairment
Improper implementation of the wiring harness may cause
mechanical stress.
Protect the cables from bending, twisting or chafing.
Install strain reliefs for the connecting cables.
Surges resulting from missing protection or fusing
Surges may cause malfunctions or damage to the product.
Protect the voltage inputs from surges according to the re-
quirements.
Ensure that the device is handled in accordance with ESD
regulations.
Electrical connection | 6
WARNING
NOTICE
NOTICE