8.6
Standard menu
The standard menu provides access to commonly used parameters. For parameter details, see Parameter descriptions on page 53.
Table 8-3 Standard menu
Parameter Group
1 - Primary Motor Settings
2 - Start/Stop Modes-1
3 - Digital Inputs
4 - Digital Outputs
5 - Protection Settings
6 - Protection Delays
7 - Set Points
48
Electrical
Keypad
Quick Start
Installation
and Status
Commissioning
M
1A
Motor Full Load Current
M
2A
Start Mode
2B
Current Limit
2C
Initial Current
2D
Start Ramp Time
2H
Stop Mode
2I
Stop Time
2O
Auto-Start Type
2P
Auto-Start Time
2Q
Auto-Stop Type
2R
Auto-Stop Time
M
3A
Input A Function
3B
Input A Name
3C
Input A Trip
3D
Input A Initial Delay
3E
Input A Trip Delay
3F
Input B Function
3G
Input B Name
3H
Input B Trip
3I
Input B Initial Delay
3J
Input B Trip Delay
M
4A
Relay A Action
4B
Relay A On Delay
4C
Relay A Off Delay
4D
Relay B Action
4E
Relay B On Delay
4F
Relay B Off Delay
4G
Relay C Action
4H
Relay C On Delay
4I
Relay C Off Delay
M
5A
Excess Start Time
5D
Phase Sequence
5E
Underpower
5F
Overpower
M
6B
Underpower Delay
6C
Overpower Delay
M
7A
Low Current Flag
7B
High Current Flag
7C
Motor Temperature Flag
Operation
Programming
Diagnostics Application
Parameters
Technical
Maintenance Options
Examples
Data
Default Value
Model dependent
Constant Current
350%
350%
00:10 (minutes:seconds)
Coast To Stop
00:03 (minutes:seconds)
Off
00:01 (hours:minutes)
Off
00:01 (hours:minutes)
Starter Disable
Starter Disable
Always Active
00:00 (minutes:seconds)
00:00 (minutes:seconds)
Input Trip (N/O)
Input Trip
Always Active
00:00 (minutes:seconds)
00:00 (minutes:seconds)
Main Contactor
00:00 (minutes:seconds)
00:00 (minutes:seconds)
Run
00:00 (minutes:seconds)
00:00 (minutes:seconds)
Trip
00:00 (minutes:seconds)
00:00 (minutes:seconds)
00:20 (minutes:seconds)
Any Sequence
20%
400%
00:05 (minutes:seconds)
00:00 (minutes:seconds)
50%
100%
80%
Digistart D3 User Guide
Issue: F