Function
3F
Input B Function
3G
Input B Name
3H
Input B Trip
3I
Input B Initial Delay
3J
Input B Trip Delay
See Pr 3A to 3E for details of parameter options.
No
Function
3K
Input C Function
3L
Input D Function
See Pr 3A for details of parameter options.
Inputs C and D are only available if the input/output expansion card is installed.
NOTE
No
Function
3M
Local/Remote
Selects when the LCL/RMT button can be used to switch between local and remote control, and enables or disables the local
control buttons and remote control inputs.
The STOP button on the keypad is always enabled.
LCL/RMT Anytime
LCL/RMT When Off
Local Control Only
Remote Control Only
The STOP button on the keypad is always enabled. When using two-wire remote control, the soft starter will restart if
the remote start/stop and reset inputs are still active.
WARNING
No
Function
3N
Remote Reset Logic
Selects whether the Digistart D3's remote reset input (terminals DI3, +24V) is normally open or normally closed.
No
Function
3O
Comms in Remote
Selects whether the starter will accept Start and Stop commands from the serial communication network when in Remote mode.
The Reset, Force Comms Trip and Local/Remote Control commands are always enabled.
Digistart D3 User Guide
Issue: F
Electrical
Keypad
Quick Start
Installation
and Status
Commissioning
Motor Set Select, Input Trip (N/O), Input Trip
(N/C), Local/Remote Select, Emergency
Run, Starter Disable, Jog Forward, Jog
Input Trip, Low Pressure, High Pressure,
Pump Fault, Low Level, High Level, No
Flow, Starter Disable, Controller, PLC,
Always Active, Operating Only, Run Only
00:00 to 30:00 (minutes:seconds)
00:00 to 04:00 (minutes:seconds)
Motor Set Select, Local/Remote Select,
Emergency Run, Starter Disable, Off
LCL/RMT Anytime, LCL/RMT When Off,
Local Control Only, Remote Control Only
LCL/RMT button is always enabled.
LCL/RMT button is enabled when the starter is off.
All remote inputs are disabled.
Local control buttons ( START , RESET , LCL/RMT ) are disabled.
Normally Closed (N/C), Normally Open
Disable Control in RMT, Enable Control in
Operation
Programming
Diagnostics Application
Range
Reverse
Vibration
Range
Range
Range
(N/O)
Range
RMT
Technical
Maintenance Options
Examples
Data
Default
Input Trip (N/O)
Input Trip
Always Active
00:00
Default
Off
Default
LCL/RMT Anytime
Default
Normally Closed (N/C)
Default
Enable Control in RMT
57