No
Function
8H
Analog Output B
8I
Analog B Scale
8J
Analog B Maximum Adjustment
8K
Analog B Minimum Adjustment
See Pr 8D to 8G for details of parameter options.
Analog Output B is only available if the input/output expansion card is installed.
NOTE
8.8.10 Group 9 - Display
No
Function
9A
Languages
Selects which language the keypad will use to display messages and feedback.
No
Function
9B
User Screen - Top Left
Selects which information will be displayed on the programmable monitoring screen.
Blank
Starter State
Motor Current
Motor pf
Mains Frequency
Motor kW
Motor HP
Motor Temp
kWh
Hours Run
Analog Input
Motor kVA
% Rated kW
Motor Parameter Set
No
Function
9C
User Screen - Top Right
9D
User Screen - Bottom Left
9E
User Screen - Bottom Right
No
Function
9F
Graph Data
Selects which information the graph will display. See Pr 8D for details of parameter options.
62
Electrical
Keypad
Quick Start
Installation
and Status
Commissioning
Current (% FLC), Motor Temp (%), Motor
kW (%), Motor kVA (%), Motor pf, Voltage
English, Français, Italiano, Deutsch,
Blank, Starter State, Motor Current, Motor
pf, Mains Frequency, Motor kW, Motor HP,
Motor Temp, kWh, Hours Run, Analog Input,
Motor kVA, % Rated kW, Motor Parameter
Displays no data in the selected area, allowing long messages to be shown
without overlapping.
The starter's operating state (starting, running, stopping or tripped). Only
available for top left and bottom left positions on the screen.
The average current measured on three phases.
The motor's power factor, measured by the soft starter.
The average frequency measured on three phases.
The motor's running power in kilowatts.
The motor's running power in horsepower.
The motor's temperature, calculated by the thermal model.
The number of kilowatt hours the motor has run via the soft starter.
The number of hours the motor has run via the soft starter.
The level of analog input A (see Pr 8A to 8C ). This setting is only available if the
input/output expansion option is installed.
The motor's apparent running power in kVA.
The motor's running power as a percentage of rated kW. Power factor is
assumed to be 1.0 at 100% kW.
Whether the starter is controlling the motor using the primary motor set (M1) or
the secondary motor set (M2).
Blank, Motor Current, Motor pf, Mains
Frequency, Motor kW, Motor HP, Motor
Temp, kWh, Hours Run, Analog Input, Motor
Blank, Starter State, Motor Current, Motor
pf, Mains Frequency, Motor kW, Motor HP,
Motor Temp, kWh, Hours Run, Analog Input,
Blank, Motor Current, Motor pf, Mains
Frequency, Motor kW, Motor HP, Motor
Temp, kWh, Hours Run, Analog Input, Motor
Current (% FLC), Motor Temp (%), Motor
kW (%), Motor kVA (%), Motor pf
Operation
Programming
Diagnostics Application
Range
(%Mains)
0-20, 4-20 mA
0 to 600%
Range
Español, Chinese
Range
Set
Range
kVA, % Rated kW
Motor kVA, % Rated kW
kVA, % Rated kW
Range
Technical
Maintenance Options
Examples
Data
Default
Current (% FLC)
4-20 mA
100%
0%
Default
Default
Motor Current
Default
Motor pf
Hours Run
kWh
Default
Current (% FLC)
Digistart D3 User Guide