8.8

Parameter descriptions

8.8.1
Notes on optional parameters
The following sections provide a description for all the parameters, whether available by default or optional. Optional parameters are
only available if the relevant option card is fitted to the soft starter. For a detailed list of optional parameters, refer to the table below.
Table 8-5 Optional parameters
No
Function
3K
Input C Function
3L
Input D Function
4J
Relay D Action
4K
Relay E Action
4L
Relay F Action
5K
Ground Fault Level
6H
Ground Fault Delay
8A
Analog Input Trip
8B
Analog Input Scale
8C
Analog Trip Point
8H
Analog Output B
8I
Analog B Scale
8J
Analog B Maximum Adjustment
8K
Analog B Minimum Adjustment
14B
RTD/PT100 B °C
14C
RTD/PT100 C °C
14D
RTD/PT100 D °C
14E
RTD/PT100 E °C
14F
RTD/PT100 F °C
14G
RTD/PT100 G °C
16P
Ground Fault
16R
RTD/PT100 B
16S
RTD/PT100 C
16T
RTD/PT100 D
16U
RTD/PT100 E
16V
RTD/PT100 F
16W
RTD/PT100 G
8.8.2
Group 1 - Primary Motor Settings
The motor data parameters are critical to the correct operation of the soft starter's thermal model, and to the motor
overload protection. Always set Pr 1A to suit the motor's characteristics. The default settings of Pr 1B , 1C and 1D are
WARNING
suitable for most applications. Consult the motor datasheet before changing these settings.
No
Function
1A
Motor Full Load Current
Matches the starter to the connected motor's full load current. Set to the full load current (FLC) rating shown on the motor
nameplate.
When connecting in inside delta, enter the motor full load current (FLC) for Pr 1A . The Digistart D3 will automatically detect whether
the motor is connected in-line or inside delta and will calculate the correct inside delta current level.
No
Function
1B
Locked Rotor Current
Sets the locked rotor current of the connected motor, as a percentage of full load current. Set according to the motor datasheet.
Digistart D3 User Guide
Issue: F
Electrical
Keypad
Quick Start
Installation
and Status
Commissioning
NOTE
NOTE
NOTE
NOTE
NOTE
NOTE
NOTE
Operation
Programming
Diagnostics Application
Option card required
Inputs C and D are only available if the input/output expansion
card is installed.
Outputs D, E and F are only available if the input/output
expansion card is installed.
Ground fault protection is only available if the RTD/PT100 and
ground fault protection card is fitted.
The analog input is only available if the input/output expansion
card is installed.
Analog Output B is only available if the input/output expansion
card is installed.
PT100 inputs B to G are only available if the RTD/PT100 and
ground fault protection card has been installed.
Ground Fault and PT100 inputs B to G are only available if the
RTD/PT100 and ground fault protection card has been installed.
Range
Model dependent
Range
400 to 1200% FLC
Technical
Maintenance Options
Examples
Data
Default
Model dependent
Default
600%