Modulex EXT Commercial Series Boilers User Manual
CHAPTER 6: Operation of the E8 Controller
TABLE 6-7: 0-10V Signal with Slope and Temperature
Curve
U1
0
2.0 V
1
2.5 V
2
2.5 V
3
2.5 V
4
4.0 V
5
4.0 V
6
4.0 V
7
4.0 V
8
4.0 V
9
4.0 V
10
4.0 V
11
4.0 V

6.10.2 Setting of DHW Circuit

6.10.2.1

Operation of Pumps In Parallel

Heating pump operation during DHW production.
EXPERT menu
6.10.2.2

Use of a DHW Storage Tank Thermostat (On/Off)

To use an ON - OFF thermostat instead of DHW sensor.
⇒ Hot Water ⇒
EXPERT menu
6.10.2.3

Antilegion

Activation of an antilegion program.
⇒ Hot Water
EXPERT menu
6.10.2.4

Setting for Solar Panel Use

Use a PT 1000 sensor as a solar panel sensor.
EXPERT menu ⇒ Solar/ MF ⇒ FUNC RELAY 4 "23"

6.11 ACCESS CODE SETTING

To set the access code, press the Programming button to enter the first parameter, use the data
knob to select a number, and then press the Programming button to accept the value. Repeat
this procedure for each code number position.
Page 108 of 144
09/15/2017
U2
10.0 V
0.3 V
0.3 V
0.3 V
0.1 V
0.1 V
0.1 V
0.1 V
0.1 V
0.1 V
0.1 V
0.1 V
⇒ F-PUMP PARAL "00,01,02,03"
Hot Water
THER IMPUT "01"
ANTILEGION "01"
Figure 6-11: Setting the Access Code
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913
Phone: 800-526-0288
T1
T2
32° F
194° F
100° F
176° F
100° F
167° F
100° F
113° F
68° F
185° F
68° F
167° F
68° F
131° F
68° F
189° F
68° F
189° F
68° F
163° F
68° F
127° F
68° F
194° F
UA
2.0 V
5.0 V
5.0 V
5.0 V
5.0 V
5.0 V
5.0 V
5.0 V
5.0 V
5.0 V
5.0 V
5.0 V
OMM-0095_0H
GF-139