Mitsubishi Electric CITY MULTI PUMY-P112VKM6 Service Manual page 60

Advertisement

5109 (U4): HIC pipe temperature thermistor (TH2) open/short
Abnormal points and detection methods
TH2 is found to be open/short.
Open:
−40°C [−40°F] or less
Short:
90°C [194°F] or more
TH2:
Thermistor <HIC pipe>
Diagnosis of failure
Check the wiring and connector connection of
TH2.
Is there any abnormality such as
disconnection, looseness or break-
age?
Disconnect the connector to check the resis-
tance of TH2 using a multimeter.
Is the detected resistance normal?
Check the temperature of TH2.
Is the detected temperature normal?
OCH790 _60
Yes
No
No
Yes
The detected temperature of TH2 can be displayed by an
operation of SW1 on the outdoor multi controller circuit board.
ON
OFF
1 2 3 4 5 6 7 8
No
Yes
Causes and checkpoints
• Disconnection or contact failure of connectors
• Faulty thermistor
• Defective outdoor multi controller circuit board
Connect the wiring/connector properly.
Replace it in the case of breakage.
Replace the thermistor.
SW1 Setting
Display on LED1, 2
Unit
–99.9–999.9
°C
Replace the outdoor multi controller circuit board
(Malfunction of thermistor circuit).
No abnormality
(A connector contact failure is suspected.)
The black square (■) indicates a switch position.